Stainless-steel process tanks and pipework in an industrial plant
ORAKEM / Closed loops

Closed loop, chilled water and district cooling treatment across the GCC

Protect chilled-water, hot-water and district cooling networks for decades, with corrosion and bacteria under control and proven by monthly data.

                                                  Closed systems lose little water, so problems build slowly and out of sight. Corrosion products turn into sludge, bacteria grow in low-flow zones, and by the time a strainer blocks or a heat-exchanger plate fouls, the damage has spread across the network. ORAKEM treats chilled-water, hot-water, glycol and district cooling loops with programmes designed for every metal in the system and checked on a fixed schedule.

                                                  Why closed loops need more than a top-up of inhibitor

                                                  A new loop is full of mill scale, welding residue and oil. Without proper flushing and passivation, these become the starting point for corrosion from the first day of operation.

                                                  Once running, the risks are general corrosion of steel, attack on copper and aluminium parts, corrosion under deposits caused by bacteria, and the slow loss of inhibitor through small leaks and make-up. In district cooling, one plant can feed hundreds of buildings, so water-quality problems travel.

                                                  We set inhibitor reserves for the metals in your system, control bacteria and oxygen ingress, and track iron, copper, conductivity and microbiology every month. Side-stream filtration and make-up metering are recommended where they pay back.

                                                  Problems we solve

                                                  • Corrosion of steel, copper and aluminium parts
                                                  • Black or red sludge and blocked strainers
                                                  • Bacteria and corrosion under deposits
                                                  • Fouled plate heat exchangers and chiller tubes
                                                  • Inhibitor loss through leaks and make-up
                                                  • Debris and residues in new or extended networks

                                                  What we measure and report

                                                  • Iron and copper levels
                                                  • Inhibitor reserve
                                                  • Total bacteria and sulphate-reducing bacteria
                                                  • Make-up water volume
                                                  • Conductivity, pH and suspended solids

                                                  Treatments in this programme

                                                  • Corrosion inhibition
                                                  • Organic treatment for district cooling and heating
                                                  • Food-grade treatment
                                                  • Microbiological control
                                                  • Glycol and antifreeze protection
                                                  • Pre-commissioning cleaning and passivation

                                                  Closed loops and district cooling across the region

                                                  District cooling networks, hotels, hospitals, malls, data centres and industrial chilled-water systems in the UAE (Dubai, Abu Dhabi, Sharjah), Saudi Arabia (Riyadh, Jeddah, Dammam), Oman (Muscat, Sohar), Qatar (Doha), Kuwait, Bahrain, Iraq, Jordan, Lebanon and Egypt run for decades on the same loop water. We flush and passivate new systems, treat running loops, and supply inhibitors and inhibited glycol concentrates.

                                                  How we work

                                                  1

                                                  Site survey

                                                  We review the system, operating data and current treatment costs.

                                                  2

                                                  Water analysis

                                                  Full water and deposit analysis, with scale projection where it applies.

                                                  3

                                                  Agreed KPIs

                                                  Targets are set with you before start-up.

                                                  4

                                                  Monthly report

                                                  Field tests and results reviewed every month, in writing.

                                                  Frequently asked questions

                                                  Do you flush and passivate new systems?

                                                  Yes. Before handover, the new network is cleaned to remove oil, debris and mill scale, then passivated so the treatment programme starts on clean metal. Test results are provided for the handover file.

                                                  Can you treat district cooling networks?

                                                  Yes, on the plant side and the network side, including energy transfer stations, with sampling points agreed so that problems can be traced to their source.

                                                  How do we know if a closed loop is leaking?

                                                  Make-up volume is the clearest sign. A water meter on the make-up line, read monthly together with inhibitor levels, shows when fresh water is entering the loop.

                                                  Do you treat glycol systems?

                                                  Yes. Glycol loops need regular checks on glycol strength, pH and inhibitor condition, because degraded glycol turns acidic and corrosive.

                                                  Do you supply closed-loop inhibitors and glycol?

                                                  Yes. Nitrite, nitrite-free and organic inhibitors and inhibited glycol concentrates are available by the drum, IBC or bulk, with TDS, SDS and a certificate of analysis.

                                                  Which countries do you cover?

                                                  We supply and support customers directly across the GCC and the Middle East: the UAE (Dubai, Abu Dhabi, Sharjah), Saudi Arabia (Riyadh, Jeddah, Dammam), Oman (Muscat, Sohar), Qatar (Doha), Kuwait, Bahrain, Iraq, Jordan, Lebanon and Egypt. Products ship in drums, IBCs or bulk, and our engineers reply within one working day.

                                                  Where we work: UAE · Saudi Arabia · Oman · Qatar · Kuwait · Bahrain · Iraq · Jordan · Lebanon · Egypt

                                                  Get a free review of your system

                                                  Send us your water analysis or operating data. An engineer replies within one working day.

                                                  Book a site survey

                                                                                                                      Book a site survey
                                                                                                                      WhatsApp us