Water treatment plant pump and pipework
ORAKEM / TSE cooling towers

TSE Cooling Tower Water Treatment

Use treated sewage effluent as make-up without paying for it in fouling, corrosion or Legionella risk.

                                                              Treated sewage effluent (TSE) saves potable and desalinated water, and district cooling plants and industrial sites across the UAE use it as cooling tower make-up. It is also harder water to treat. It carries more nutrients, phosphate, ammonia, suspended solids and organic matter than potable water, and its quality can change from day to day. ORAKEM builds programmes for TSE-fed towers around those variations.

                                                              What changes when your tower runs on TSE

                                                              Nutrients and organic matter feed bacteria and biofilm, so microbiological control comes first. Ammonia consumes chlorine and changes how oxidising biocides behave, which is why the biocide strategy for TSE differs from one for potable make-up.

                                                              Phosphate and suspended solids raise the risk of deposits, especially calcium phosphate on hot surfaces. Higher chloride and sulphate make the water more corrosive to steel and copper alloys.

                                                              Many sites add side-stream filtration, softening or RO polishing before the tower. We review the whole make-up treatment train, set cycles from the real water quality and adjust the programme when the TSE changes, with the data to show it.

                                                              Problems we solve

                                                              • Biofilm and bacteria fed by nutrients
                                                              • Calcium phosphate and suspended-solids deposits
                                                              • Higher corrosion from chloride and sulphate
                                                              • Biocide demand from ammonia
                                                              • Variable make-up quality
                                                              • Legionella risk in warm, nutrient-rich water

                                                              What we measure and report

                                                              • Make-up water quality on every visit
                                                              • Cycles of concentration
                                                              • Corrosion rate on coupons
                                                              • Total bacteria and Legionella results
                                                              • Deposit monitoring on heat-transfer surfaces

                                                              Treatments in this programme

                                                              • Scale and corrosion inhibition
                                                              • Oxidising biocide programme
                                                              • Non-oxidising biocide programme
                                                              • Biofilm and biofouling control
                                                              • Dispersant and deposit control
                                                              • Oil and process-leak control
                                                              • Legionella risk control

                                                              How we work

                                                              1

                                                              Site survey

                                                              We review the system, operating data and current treatment costs.

                                                              2

                                                              Water analysis

                                                              Full water and deposit analysis, with scale projection where it applies.

                                                              3

                                                              Agreed KPIs

                                                              Targets are set with you before start-up.

                                                              4

                                                              Monthly report

                                                              Field tests and results reviewed every month, in writing.

                                                              Frequently asked questions

                                                              Is TSE suitable for cooling tower make-up?

                                                              Yes, with the right treatment and monitoring. TSE is widely used in UAE cooling towers. The programme has to allow for its higher nutrient, phosphate and ammonia content.

                                                              Can we run high cycles on TSE?

                                                              Usually fewer than on low-hardness water, because phosphate, silica and chloride limits are reached sooner. We set the limit from your own TSE analysis and any polishing step.

                                                              How do you handle changing TSE quality?

                                                              We test the make-up on every visit, keep a trend of the key parameters and agree action levels with your operators, so the programme is adjusted before problems build up.

                                                              Do you also treat the TSE polishing plant?

                                                              Yes. We support side-stream filters, softeners and RO polishing units with antiscalants, cleaning chemicals and biocides.

                                                              Where we work: UAE · Saudi Arabia · Oman · Qatar · Kuwait · Bahrain · Iraq · Jordan · Lebanon · Egypt

                                                              Get a free review of your system

                                                              Send us your water analysis or operating data. An engineer replies within one working day.

                                                              Book a site survey

                                                                                                                      Book a site survey
                                                                                                                      WhatsApp us